HVAC System Sizing Calculator — Tonnage Estimator

Estimate the required HVAC system size (in tons of cooling/heating) for a residential or light commercial space using a simplified Manual J–style load calculation.

Formulas Used

Total Cooling Load (BTU/hr):

Q_total = (Q_env + Q_solar + Q_occ + Q_int + Q_inf) × F_climate × F_insulation × F_stories × F_shade × F_internal

  • Envelope Conduction: Q_env = Volume × U_eff × ΔT — where Volume = sqft × ceiling height (ft³), U_eff = 0.133 BTU/(hr·ft³·°F), ΔT = 20°F design difference
  • Solar Gain: Q_solar = A_window × SHGC × I_peak × F_orientation — SHGC = 0.40 (double-pane low-e), I_peak = 200 BTU/(hr·ft²)
  • Occupant Load: Q_occ = N × 250 BTU/hr — ASHRAE sensible heat per person (light activity)
  • Internal Load: Q_int = sqft × 3.0 BTU/(hr·ft²) — residential appliance/lighting baseline
  • Infiltration: Q_inf = Volume × ACH × 1.1 × ΔT — ACH = 0.5, 1.1 = ρ·Cp for air in BTU/(ft³·°F)
  • Tonnage: Tons = Q_total / 12,000 — 1 ton of cooling = 12,000 BTU/hr
  • Equipment Sizing: Round up to nearest 0.5-ton increment per industry practice

Assumptions & References